Highest quality standards are achieved through the implementations of latest technology, decades of experience and everlasting moral values , which have helped us to retain our customers as well as multiply them.
DESCRIPTION | |
The shunts are designed to comply with the requirements of IS1248 / DIN43703 & DIN43780. The shunt provides an accurate d.c. millivolt signal, exactly proportional to the system current |
FEATURES | |
• | Rating 1A to 15000A |
• | Riveted and soldered construction |
• | In-line bus bar mounting |
• | Very low temperature coefficient |
• | High overload withstand |
• | Shock and vibration Proof |
• | Long term stability |
• | TYPE 1) Insulated mounting 2) "I" Section 3) "L" Section 4) "T" Section |
Ranges 1, 1.5,2,2.5, 3,4,5,6, 10, 15,20,25, 30 Amp. 30, 40, 50, 60, 75, 80, 100, 120, 150Amp. 200, 250, 300, 400, 500, 600, 750, 800, 1000, 1200, 1500, 2000, 2500, 3000Amp. 4000, 5000, 6000, 7500, 8000, 10000, 12000, 15000Amp. |
• | ACCURACY | ± 0.5% |
• | CONTINUOUS OVER LOAD |
20% rated current |
• | 5 SECONDS WITHSTAND | 10 times for 1 A to 500 Amp. 5 times for 600A to 2000Amp. 2 times for 2500A to 15000Amp. |
• | TEMP. COEFFICIENT | 0.002% per °C. |
• | AMBIENT TEMP. | Calibration at 23°C. |
• | OPERATING TEMP. | -10°C to 55°C. |
• | STORAGE TEMP. | -20°C to 70°C |
• | MAXIMUM LOAD | The load should not exceed 0.1% of the nominal current rating for specified accuracy. |
• | MILLIVOLT | 50mV, 60mV, 75mV, l00mV, 150mV, 300mV (standard) Other mV outputs on request. |
NOTE : |
Two cables of 1 meter length with 1.5mm cross sectional area are provided. This corresponds to a total resistance of 0.026 ohms. The instruments are calibrated with this resistance and consequently the cable length must not be changed. If different length or resistances are required, please indicate while ordering. |
INSTALLATION |
The best performance is guaranteed if the following points are observed. |
1) Shunts may be mounted horizontally or vertically. Horizontal mounting gives the best heat dissipation. |
2) Utilize the full end block surface area. |
3) Ample ventilation should be provided. |
4) Busbar should be adequately rated, cleaned & coated with a thin layer of silicon grease applied to the contact surface area. |
5) Bolts and nuts must be carefully tightened. |
CAUTION |
Shunts are not insulated & protection against accidental contact may be necessary in order to comply with Health & Safety regulations. |
Ordering information |
1) Current rating 2) Millivolt output 3) Length of the cable |
Rated Current Amps. |
Dim 'A' Max. | Dim 'B1' |
Dim 'B2' |
Dim 'B3' |
Dim 'C1' |
Dim 'E' | Dim 'H' | |||||||||
(mV) | (mV) | (mV) | ||||||||||||||
60 | 75 | 100 | 150 | 300 | 60 | 75 | 100 | 150 | 300 | 60/75 | 100~300 | |||||
1~30 | 90 | 90 | 90 | 90 | 90 | 20 | - | - | 8 | 80 | 80 | 80 | 80 | 80 | 8 | 8 |
40~150 | 100 | 120 | 145 | 225 | 285 | *20 | - | - | 8 | 80 | 100 | 125 | 205 | 365 | 8 | 8 |
200~300 | 145 | 165 | 190 | 270 | 430 | 30 | 15 | - | 10 | 105 | 125 | 150 | 230 | 390 | 30 | 30 |
400~750 | 145 | 165 | 190 | 270 | 430 | 40 | 20 | - | 10 | 105 | 125 | 150 | 230 | 390 | 30 | 30 |
800~1000 | 165 | 185 | 210 | 290 | 450 | *60 | 30 | - | 10 | 115 | 135 | 160 | 240 | 400 | 30 | 30 |
1200~1500 | 165 | 185 | 210 | 290 | 450 | 90 | 21 | 48 | 10 | 115 | 135 | 160 | 240 | 400 | 30 | 30 |
1600~3000 | 165 | 185 | 210 | 290 | 450 | 120 | 30 | 60 | 10 | 115 | 135 | 160 | 240 | 400 | 30 | 60 |
4000~5000 | 165 | 185 | 220 | 300 | 460 | 120 | 30 | 60 | 15 | 115 | 135 | 170 | 250 | 410 | 60 | 130 |
6000~7500 | 175 | 195 | 220 | 300 | 460 | 154 | 25 | 52 | 25 | 125 | 145 | 170 | 250 | 410 | 130 | 130 |
8000~10000 | 185 | 205 | - | - | - | 206 | 25 | 52 | 30 | 135 | 155 | 180 | 260 | 420 | 170 | - |
12000~15000 | 185 | 205 | - | - | - | 310 | 25 | 52 | 30 | 135 | 155 | 180 | 260 | 420 | 170 | - |
Rated Current Amps. |
Current Terminal Dim. |
No. of Current Terminal |
No. of Current Terminal |
1~30 | M 5x12 | 2 x 1 | - |
40~150 | M 8x12 | 2 x 1 | 15 |
200~300 | M 12x40 | 2 x 1 | 20 |
400~750 | M 16x45 | 2 x 1 | 25 |
800~1000 | M 20x50 | 2 x 1 | 40 |
1200~1500 | M 16x45 | 2 x 2 | 40 |
1600~3000 | M 20x50 | 2 x 2 | 40 |
4000~5000 | M 20x50 | 2 x 2 | 40 |
6000~7500 | M 20x75 | 2 x 3 | 40 |
8000~10000 | M 20x85 | 2 x 4 | 40 |
12000~15000 | M 20x85 | 2 x 6 | 40 |
UPTo 30 Amps. | 40 A To 150 A | 200 A To 1000 A |
1200 TO 3000 A | 4000 A To 5000A 6000 A to 7500 A shunts have 3 Boltsat each terminal spaced at lateral distance B3 |
8000 A To 10000 A 12000 A to 15000 A shunts have 6 Bolts at each terminal spaced at lateral distance B3 |
8000 A To 10000 A 12000 A to 15000 A shunts have 6 Bolts at each terminal spaced at lateral distance B3 |
||
(All Dimension are in mm) |
Note : |
1) Dimension A, E, H are the same for 50mV shunt & 60mV shunt. |
2) Unless specified tolerance for mounting dimensions (Dim "E") shall be of ±1.5mm upto 1500A rating & ± 2.0mm for the rating above 1500A. |
3) Maximum value of 'H' is specified, Minimum value is equal to corresponding value of 'C1'. |
4) *Dimension 20 & 60mm is for 60/75mV and 25 & 70 mm respectively for 100~300mV. |
5) The consumption of measuring instusments should not exceed 500 microwatts for interchangeable shunts. |
* To embrace new technologies and methods. * To give unsurpassed products and services to the clients. * To constantly look for improvement and changes.